Hanna BL-983315-1 TDS Mini Controller 0.00 to 199.9 mg/L
Users may choose from automatic or manual dosing modes. When in automatic mode the dry contact relay is activated when a reading is above the set point. The relay can be used to supply power to a dosing pump or a solenoid connected to a valve. The BL-983315 can also be used to monitor the quality of water produced from ion exchange, reverse osmosis (RO) or distillation.
The BL-983315 uses a 0.5 conversion factor in which 1.0 μS/cm = 0.5 ppm.
● Multicolour LED Indicator
● Fire Retardant Casing
● Fire Retardant Casing
Adjustable Dry Contact Dosing Relay
The BL-983315 features a dosing relay that is activated when the reading is above a user programmable set point.
Programmable Overdose Protection
For enhanced safety the mini controller can be programmed to deactivate the dosing relay if the set point is not reached within a specified time interval. The overdosing timer is programmable from 5 to 30 minutes or disabled.
Relay Control Override
With the flick of a switch the mini controller’s relay can be disabled (Off), placed in control (Auto), or be activated for manual operation (On) which is useful for priming a dosing pump.
Multi-colour LED Indicator
Multi-colour LED indicator allows an operator to quickly check the status of the controller.
- Green = Meter in measurement mode and reading is below the set point
- Orange/Yellow = Reading is above the set point and the relay is activated
- Blinking Red = Indicates an alarm condition such as when the maximum dosing time has been exceeded
Fuse Protected Dosing Contacts
The relay dosing contact is rated for up to a 2A load and is fuse protected.
Labelled Termination Connections
Quick-connect terminal blocks are clearly labelled for easy connection to power, conductivity probe and relay that can be used to operate a dosing pump, valve, audible alarm, or light.
1/2″ (13mm) NPT Male Threaded Amperometric Probe for Mounting In-line*
The BL-983315 mini controller uses the HI-7634-00 conductivity probe that is available with different cable lengths.
*HI-7634-00 is not included and must be ordered separately.
Specification Hanna BL-983315-1 TDS Mini Controller :
Range | 0.0 to 199.9 µS/cm | |
Resolution | 0.1 µS/cm | |
Accuracy | ±2% F.S. | |
TDS Conversion Factor | 0.5 | |
Probe | HI-7634-00 (not included) | |
Temperature Compensation | Automatic, 5 to 50°C (41 to 122°F) with ß = 2%/°C | |
Calibration | manual, with CAL trimmer | |
Dosing Relay | max 2A (fuse protected), 250 Vac | |
Dosing Selection | Relay activated (contact closed) when the measurement reading is greater than the setpoint | |
Setpoint | adjustable from 0 to 199.9 µS/cm | |
Overtime | adjustable, typically from 5 to approx. 30 minutes | |
Power Supply | 12 VDC adapter (included) | |
Dimensions | 83 x 53 x 99 mm (3.3 x 2.1 x 3.9″) | |
Weight | 200 g (7.1 oz.) |
Hanna BL-983315-1 Manuals
PT. JAVA SURVEY INDO adalah distributor dan Supplier Hanna BL-983315-1 TDS Mini Controller di Jawa Barat & Jakarta dan juga menjual Brand HANNA diantaranya Hanna BL-983318-1, Hanna HI 780, Hanna HI-772-26, Hanna HI-96811, Hanna HI-2040, Hanna HI-98100, Hanna HI-7001L, Hanna HI-1048B, Hanna HI-97742, Hanna HI-93746-03, Hanna HI-747, Hanna HI-8033, Hanna HI-95762-01, Hanna HI-97770, Hanna HI-7031/1G, Hanna HI-701-11, Hanna HI-981036, Hanna HI-981030, Hanna HI-98164, Hanna HI-720, Hanna HI-98318,Hanna BL-931700-1, Hanna HI-97500, Hanna HI-709 dll. Dengan pelayanan terbaik di Jawa Barat & Jakarta. Kami juga menjual alat kapal dan alat komunikasi antara lain ICOM, Hytera, SAMYUNG, MOTOROLA, FURUNO, SHAKESPEARE, THURAYA, INMARSAT, IRIDIUM, KODEN, dll tersedia juga alat uji lingkungan dan alat survey NIKON, TOPCON, SOKKIA, RUIDE, SOUTH, CHC , IRTEK, BUSHNELL0663 KONSTAN. Bisa juga melalui email ke [email protected] Atau lihat produk kami lainnya di sini., BENETECH, LUTRON, SMART SENSOR, FLUKE, KYORITSU, HANNA, EXTECH dll. Lihat produk kami lainnya di sini KMT, SGI. Silakan hubungi kami melalui Whatsapp 0813-9895-5475.